YOKOGAWA: Upper link

Communicates with the Yokogawa PLC via the upper link.


For FA-M3"V" series

For Ethernet with built-in PLC

F3SP71-4S for IP address 192.168.1.10

  • Connect to the PLC using WideField3.
  • Assign the IP address in the ETHERNET settings of the CPU properties.
    When setting up the IP setting up the IP on the irBoard, specify the IP address provided here.
  • Click the OK button to save the file.
  • Select Online -> Download [PC-CPU] -> CPU Properties from the menu, then download the saved file to the PLC.
  • Turn the power back on.

For Ethernet interface module LE-11

F3SP58-6S + LE11-OT with IP address 192.168.1.10

  • Set the IP address before turning on the PLC.
  • The IP address is configured using the rotary switch on the side of the LE11-0T module. Set C0 A8 01 0A for 192.168.1.10 in hexadecimal.
    When setting the IP in irBoard, specify the IP address provided here.
  • Turn the power back on.
  • No special configuration is necessary for WideField2 projects.